Smart-UPS On-Line SRT 2200 VA and SRT 3000 VA
Technical specifications
apc.com10
Product feature
SRT2200XLI
SRT2200RMXLI
SRT3000XLI
SRT3000RMXLI
SRT3000XLW-IEC
SRT3000RMXLW-IEC
Output
Power rating
2200 VA/1980 W
3000 VA/2700 W
Nominal output voltage
230 V (220 V, 240 V user selectable)
230 V (208 V, 220 V, 240 V
user selectable)
Output frequency
50/60 Hz ± 3 Hz (auto sense) 50/60 Hz ± 0.1 Hz (user selectable)
Topology
Double-conversion online
Online efficiency at full load (typical)
92%
Green mode efficiency at full load (typical)
96%
97%
Output connections (switched groups)
(8) IEC 320 C13
(2) IEC 320 C19
(4) IEC320 C13
(2) IEC320 C19
Input
Nominal input voltage
230 V
230 V (208 V, 220 V, 240 V
user selectable)
Input voltage range full load (half load)
160 – 275 V (100 – 275 V)
Input frequency
40 – 70 Hz auto-selecting
Input connection
IEC-60320 C20, Schuko CEE 7/EU1-16P, British BS1363A
Batteries and runtime
Battery type
Maintenance-free sealed lead-acid battery with suspended electrolyte, leak proof
Typical backup time at ½ load (min)
11.6 min
11.8 min
Typical backup time at full load (min)
3.9 min
4.0 min
Replacement battery (quantity)
APCRBC141 (1)
APCRBC152 (1)
External battery pack (tower/rack mount)
SRT72BP/SRT72RMBP
SRT96BP/SRT96RMBP
Communication and management
Interface ports
Serial (RJ45), USB (Type A) and SmartSlot
Control panel
High resolution graphical LCD display
Emergency power off (EPO)
Yes (NO/NC connections)
Physical
Rack height
85 mm, 2U
Maximum width (RM)
432 mm
432 mm
Maximum depth (RM)
585 mm
636 mm
Net weight
25 Kg
31 kg
Conformance
Regulatory
CE, VDE, RCM, and EAC, IEC/EN
62040-1, IEC/EN 62040-2
CE, VDE, RCM, and EAC, IEC/EN 62040-1, IEC/EN 62040-2,
UL-1778, FCC Part 15 Class A, CSA
Warranty
Three years electronics/two years battery